Commissioning and Fault Finding
76
11 FAULT FINDING
11.1 STARTING
Symptom Possible Remedy
Unit is inoperative
Read/Write configuration
does not operate
Check the battery and wiring to the unit. Check the DC supply. Check
the DC fuse.
Unit shuts down Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70°C. Check the DC
fuse.
Fail to Start is activated Check wiring of the S2 sensing cables. Check the start output is
correctly wired into the generator controller.
Continuous starting of S2
when in AUTO
mode.
Check that there is no signal present on the “Remote Start” input.
Check configured polarity is correct.
Check the S2 supply available and within configured limits
S2 fails to start or go on load
on receipt of Remote Start
signal.
Check S2 Fail Delay timer has timed out.
Check signal is on “Remote Start” input. Confirm correct configuration
of input is configured to be used as “Remote Start”.
11.2 LOADING
Symptom Possible Remedy
S2 supply present runs but
will not take load
Ensure S2 is available and within configured limits and a load inhibit
signal is not present on the module inputs. Check connections to the
switching device.
Note that S2 will not take load in manual mode unless there is an
active remote start on load signal.
11.3 ALARMS
Symptom Possible Remedy
Electrical Trip fault operates Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
Warning fault operates Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.