Protections
67
7.2 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the system, they serve to
draw the operators attention to an undesirable condition.
Example
1/2 Alarm
S1 Failure
Latched
Warning
In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings
and shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However some
warning alarms are latched and will need to be reset manually.
Display Reason
Auxiliary Inputs
If an auxiliary input has been configured as a warning the appropriate
LCD message will be displayed and the COMMON ALARM LED will
illuminate.
Battery Under Voltage
The DC supply has fallen below the low volts setting level for the
duration of the low battery volts timer
Battery Over Voltage
The DC supply has risen above the high volts setting level for the
duration of the high battery volts timer
Calibration Lost
The module has lost its calibration settings and must be sent back to
DSE to be re-calibrated.
Expansion Inputs
If an expansion input has been configured as a warning the appropriate
LCD message will be displayed and the COMMON ALARM LED will
illuminate.
Fail To Start
S2 has not reached the configured limits or loading voltage and
frequency before the S2 Fail Delay timer has expired.
Fail To Stop
The module has detected a condition that indicates that S2 is present
when it has been instructed to stop.
Loading Voltage Not
Reached
Indicates that the S2 voltage is not above the configured loading voltage.
S2will not take load when the alarm is present after the safety timer.
NOTE: Only applicable when S2 is configured as a generat
NOTE: Only applicable when S2 is configured as a generatNOTE: Only applicable when S2 is configured as a generat
NOTE: Only applicable when S2 is configured as a generator
or or
or
supply.
supply.supply.
supply.
Loading Frequency Not
Reached
Indicates that the S2 frequency is not above the configured loading
frequency. S2 will not take load when the alarm is present after the
safety timer.
NOTE: Only applicable when S2 is configured as a generator
NOTE: Only applicable when S2 is configured as a generator NOTE: Only applicable when S2 is configured as a generator
NOTE: Only applicable when S2 is configured as a generator
supply.
supply.supply.
supply.