Controls and Indications
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
59
6.5 TEST MODE
NOTE:- If a digital input configured to panel lock is active, changing module modes will not be
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Activate test mode be pressing the pushbutton. An LED indicator beside the button confirms this action.
Test mode will start the set(s) and parallel the mains to the generator bus to provide a Test on load function.
Depending upon configuration this can be continuous parallel or island mode operation.
6.5.1 WAITING IN TEST MODE
When in test mode, the set will not start automatically.
To begin the starting sequence, press the
button.
6.5.2 ENGINE RUNNING
Parallel operation is governed by configuration. See the previous section entitled Auto Mode: Engine Running for
further details.
In test mode, the set will continue to run on load until either:
The stop button is pressed – The generator bus breaker is opened and the set(s) are called to stop.
The auto button is pressed. The set(s) will observe all auto mode start requests and stopping timers
before beginning the Auto mode stopping sequence.