Installation
Part No. 057-120 8660 OPERATING MANUAL ISSUE 1 07/05/2010 ADM
29
4.1.3 LOAD SWITCHING AND MAINS VOLTAGE SENSING (V1)
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
39 Output relay C
1.0mm
AWG 18
Normally configured to control load switching device
(Recommend 10A fuse)
40 Output relay C
1.0mm
AWG 18
Normally configured to control load switching device
41 Output relay D
1.0mm
AWG 18
Normally configured to control load switching device
(Recommend 10A fuse)
42 Output relay D
1.0mm
AWG 18
Normally configured to control load switching device
V1
43 Mains L1 (R) voltage monitoring
1.0mm
AWG 18
Connect to Mains L1 (R) incoming supply (AC)
(Recommend 2A fuse)
44 Mains L2 (S) voltage monitoring
1.0mm
AWG 18
Connect to Mains L1 (S) incoming supply (AC)
(Recommend 2A fuse)
45 Mains L3 (T) voltage monitoring
1.0mm
AWG 18
Connect to Mains L1 (T) incoming supply (AC)
(Recommend 2A fuse)
46 Mains Neutral (N) input
1.0mm
AWG 18
Connect to Mains N incoming supply (AC)
NOTE: - The above table describes connections to a three phase, four-wire system. For alternative
wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.
4.1.4 GENERATOR BUS VOLTAGE SENSING (V2)
PIN
No
DESCRIPTION CABLE
SIZE
NOTES
V2
47
Generator Bus L1 (U) voltage
monitoring
1.0m
AWG 18
Connect to Generator Bus L1 (U) output (AC)
(Recommend 2A fuse)
48
Generator Bus L2 (V) voltage
monitoring input
1.0m
AWG 18
Connect to Generator Bus L2 (V) output (AC)
(Recommend 2A fuse)
49
Generator Bus L3 (W) voltage
monitoring input
1.0m
AWG 18
Connect to Generator Bus L3 (W) output (AC)
(Recommend 2A fuse)
50 Generator Bus Neutral (N) input
1.0m
AWG 18
Connect to Generator Bus Neutral terminal (AC)
NOTE:- The above table describes connections to a three phase, four wire system. For alternative
wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this manual.